KFM136P-2

Nickel Cadmium (NiCd) Flooded Float Service Standby – Medium Rate Float Service to Occasional Cycling Stationary Batteries, 2.4V, 0 Ah (c20), Vented Valve, Fiber Plate plate

Description

Medium discharge Rate Battery, NiCd – Multi Cell Block, Fiber Plate, 2.4V with (8) M10 terminals [129Ah (c5 to 1.14vpc), 135Ah (c5 to 1.10vpc), 134.5Ah (c5 to 1.05vpc), 136Ah (c5 to 1.00vpc)], 5.2″ L x 7.68″ W x 13.74″ H (max ht), 28.4 Lbs

Additional information

Weight 28.4 lbs
Dimensions 5.2 × 7.68 × 13.74 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.30.8090

Battery Chemistry

Nickel Cadmium (NiCd)

Battery Composition

Flooded

Battery Plate Type

Fiber Plate

Battery Valve Style

Vented

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

2

Battery Nominal DC Volts

2.4

Terminal Type

M10

Length inches

5.2

Width inches

7.68

Height inches

13.74

Weight in Lbs

28.4

AH (c5)

134.5

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Ambient Temp. Resilience

Cold to Hot

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

Float Service to Occasional Cycling

Common Applications

Harsh Electrical and Temperature Environments – Utility Switchgear and Control, Mining, Oil, Water Treatment Plant