STHP-024-4304-228-043

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 48V, 4740 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Telco/Utility/Industrial/Solar, VRLA AGM Modular Battery System, 48VDC, 24 cells arranged in 4 stack(s) of (3) 4-cell compartment painted steel module reference “T-4300HP-4×1440/MODx3”, with each containing polypropylene case cells of model T-4300HP, 9476wpc@15min., 10972wpc@10min, 4740Ah(c20), 4304Ah(c8). Battery system nominal reserve kW ratings: 315.384kWb @5min, 263.328 kWb @10min, 227.424 kWb @15min, [117.936 kWh (c1), 206.592 kWh (c8), 212.64 kWh (c10), 227.52 kWh (c20), 237.312 kWh (c24), based on nominal 2.00VPC], 188.62″W x 48.82″H x 27.99″D, 15317.7 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 15317.7 lbs
Dimensions 188.62 × 188.62 × 48.82 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

24

Battery Nominal DC Volts

48

Terminal Type

M8 lead-plated brass insert

Length inches

188.62

Width inches

188.62

Height inches

48.82

Depth inches

27.99

Weight in Lbs

15317.7

WPC (10min to 1.67vpc @ 25c)

10972

WPC (15min to 1.67vpc @ 25c)

9476

240-cell kW rating (10min)

2633.28

240-cell kW rating (15min)

2274.24

AH (c5)

3700

AH (c8)

4304

AH (c10)

4430

AH (c20)

4740

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control