STHP-192-3504-1482-166-NS

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 384V, 3860 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Datacenter/Industrial/Solar, VRLA AGM Modular Battery System, 384VDC, 192 cells arranged in 16 stack(s) of (6) 4-cell compartment painted steel module reference “T-3500HP/4”, with each containing polypropylene case cells of model T-3500HP, 7713wpc@15min., 8931wpc@10min, 3860Ah(c20), 3504Ah(c8). Battery system nominal reserve kW ratings: 2053.632kWb @5min, 1714.752 kWb @10min, 1480.896 kWb @15min, [768 kWh (c1), 1345.536 kWh (c8), 1382.4 kWh (c10), 1482.24 kWh (c20), 1548.288 kWh (c24), based on nominal 2.00VPC], 757.68″W x 79.76″H x 27.99″D, 107938.3 Lbs. Battery system furnished complete with mounting base, intercell connectors, protective front covers, and assembly hardware

Additional information

Weight 107938.3 lbs
Dimensions 757.68 × 757.68 × 79.76 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

192

Battery Nominal DC Volts

384

Terminal Type

M8 lead-plated brass insert

Length inches

757.68

Width inches

757.68

Height inches

79.76

Depth inches

27.99

Weight in Lbs

107938.3

WPC (10min to 1.67vpc @ 25c)

8931

WPC (15min to 1.67vpc @ 25c)

7713

240-cell kW rating (10min)

2143.44

240-cell kW rating (15min)

1851.12

AH (c5)

3010

AH (c8)

3504

AH (c10)

3600

AH (c20)

3860

50% DOD Cycle rating

2000

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems