Description
General Purpose Multi Cell Block battery, VRLA AGM, ABS case, 12V with (2) T2 terminals [52.8 WPC @5 min, 33.8 WPC @10 min, 27 WPC @15 min to 1.67vpc] [8Ah (c20)], 5.94″L x 2.56″W x 3.94″H (max ht), 5.18 Lbs
Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 8 Ah (c20), Regulated Valve, high porosity pure virgin lead grid plate
General Purpose Multi Cell Block battery, VRLA AGM, ABS case, 12V with (2) T2 terminals [52.8 WPC @5 min, 33.8 WPC @10 min, 27 WPC @15 min to 1.67vpc] [8Ah (c20)], 5.94″L x 2.56″W x 3.94″H (max ht), 5.18 Lbs
| Weight | 5.18 lbs |
|---|---|
| Dimensions | 5.94 × 2.56 × 3.94 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | high porosity pure virgin lead grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94HB-Non-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | T2 |
| Terminal Location | Top |
| BCI Reference | 46363 |
| Length inches | 5.94 |
| Width inches | 2.56 |
| Height inches | 3.94 |
| Weight in Lbs | 5.18 |
| WPC (10min to 1.67vpc @ 25c) | 33.8 |
| WPC (15min to 1.67vpc @ 25c) | 27 |
| 240-cell kW rating (10min) | 8.112 |
| 240-cell kW rating (15min) | 6.48 |
| AH (c5) | 6.85 |
| AH (c10) | 7.5 |
| AH (c20) | 8 |
| 50% DOD Cycle rating | 450 |
| Capacity Bracket (10 Min WPC) | 28 – 37 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | < 28 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 5 – 19 Ah (C8) |
| Capacity Bracket (C10 Ah) | 5 – 19 Ah (C10) |
| Capacity Bracket (C20 Ah) | 5 – 19 Ah (C20) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | General Purpose |