High Rate UPS battery, VRLA AGM, ABS case, 12V with (2) M6 threaded insert terminals [769 WPC @5 min, 557 WPC @10 min, 476 WPC @15 min to 1.67vpc] [Ah (c20)], 13.46″L x 6.77″W x 11.2″H (max ht), 92.4 Lbs
Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, high porosity pure virgin lead grid plate
High Rate UPS battery, VRLA AGM, ABS case, 12V with (2) M6 threaded insert terminals [769 WPC @5 min, 557 WPC @10 min, 476 WPC @15 min to 1.67vpc] [Ah (c20)], 13.46″L x 6.77″W x 11.2″H (max ht), 92.4 Lbs
| Weight | 92.4 lbs |
|---|---|
| Dimensions | 13.46 × 6.77 × 11.2 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | high porosity pure virgin lead grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M6 Threaded Insert |
| Terminal Location | Top |
| BCI Reference | 31 (tall) |
| Length inches | 13.46 |
| Width inches | 6.77 |
| Height inches | 11.2 |
| Weight in Lbs | 92.4 |
| WPC (10min to 1.67vpc @ 25c) | 557 |
| WPC (15min to 1.67vpc @ 25c) | 476 |
| WPC (20min to 1.67vpc @ 25c) | 376 |
| 240-cell kW rating (10min) | 133.68 |
| 240-cell kW rating (15min) | 114.24 |
| 240-cell kW rating (20min) | 90.24 |
| AH (c5) | 123.5 |
| 50% DOD Cycle rating | 450 |
| Capacity Bracket (10 Min WPC) | 525 – 614 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 436 – 524 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 376 – 435 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 100 – 199 Ah (C8) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | High-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Data Center UPS Systems |