LSe200

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony flat plate

Description

Switchgear / UPS Single-Cell Flooded Lead-Acid Battery, Lead Selenium Plate, 2V with (2) Lead Post with copper insert and 2 holes for dual connector terminals [396.1 WPC @15 min to 1.75vpc, 1 minute discharge current rating to 1.75vpc = 364 amps], [264Ah (c24), 214Ah (c10), 203.2Ah (c8)], 4.9″L x 8.1″W x 16.1″H, 44.9 Lbs.

Additional information

Weight 44.9 lbs
Dimensions 4.9 × 8.1 × 16.1 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony flat

Battery Valve Style

Vented

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Lead Post with copper insert and 2 holes for dual connector

Length inches

4.9

Width inches

8.1

Height inches

16.1

Weight in Lbs

44.9

WPC (10min to 1.67vpc @ 25c)

446.5

WPC (15min to 1.67vpc @ 25c)

396.1

WPC (20min to 1.67vpc @ 25c)

357.5

240-cell kW rating (10min)

107.16

240-cell kW rating (15min)

95.064

240-cell kW rating (20min)

85.8

AH (c5)

181

AH (c8)

203.2

AH (c10)

214

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Utility Switchgear and Control