LSe1400

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony flat plate

Description

Switchgear / UPS Single-Cell Flooded Lead-Acid Battery, Lead Selenium Plate, 2V with (4) Lead Post with copper insert and 2 holes for dual connector terminals [1980.7 WPC @15 min to 1.75vpc, 1 minute discharge current rating to 1.75vpc = 1412 amps], [1711.2Ah (c24), 1438Ah (c10), 1365.6Ah (c8)], 10.8″L x 8.3″W x 28.6″H, 227.6 Lbs.

Additional information

Weight 227.6 lbs
Dimensions 10.8 × 8.3 × 28.6 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony flat

Battery Valve Style

Vented

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Lead Post with copper insert and 2 holes for dual connector

Length inches

10.8

Width inches

8.3

Height inches

28.6

Weight in Lbs

227.6

WPC (10min to 1.67vpc @ 25c)

2130.7

WPC (15min to 1.67vpc @ 25c)

1980.7

WPC (20min to 1.67vpc @ 25c)

1855.3

240-cell kW rating (10min)

511.368

240-cell kW rating (15min)

475.368

240-cell kW rating (20min)

445.272

AH (c5)

1227.5

AH (c8)

1365.6

AH (c10)

1438

Capacity Bracket (10 Min WPC)

1965 – 2264 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Utility Switchgear and Control