100G81 (Medium Rate)

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 4440 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte Medium Rate [connectors sized for 2360A or less continuous current are NOT INCLUDED] Multi Purpose VRLA Tripple-paralleled battery cells used with multicell series-connected modules, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 2V, [4440Ah (c20), 4050Ah (c10), 3888Ah (c8), 3495Ah (c5), 3324Ah (c4), 3087Ah (c3), 2766Ah (c2), 2028Ah (c1)], 35.75″W x 8.59″H (max ht) x 26.38″D, 653 Lbs

Additional information

Weight 653 lbs
Dimensions 35.75 × 8.59 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

3

Battery Nominal DC Volts

2

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

35.75

Height inches

8.59

Depth inches

26.38

Weight in Lbs

653

AH (c5)

3495

AH (c8)

3888

AH (c10)

4050

AH (c20)

4440

50% DOD Cycle rating

2500

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control