12 OSP.HC 1020

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-1080) (12 OSP.HC 1020) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (4) Composite Threaded Insert terminals [2175.6 WPC @15 min to 1.67vpc],[1112Ah (c10), 1063.2Ah (c8), 1.24 S.G.], 8.46″L x 9.25″W x 27.95″H (max ht), 184.5 Lbs

Additional information

Weight 184.5 lbs
Dimensions 8.46 × 9.25 × 27.95 in
Product Discontinued?

Yes

Availability

Superseded by VM2-1080

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

9.25

Height inches

27.95

Weight in Lbs

184.5

WPC (10min to 1.67vpc @ 25c)

2353.7

WPC (15min to 1.67vpc @ 25c)

2175.6

WPC (20min to 1.67vpc @ 25c)

2016.2

240-cell kW rating (10min)

564.888

240-cell kW rating (15min)

522.144

240-cell kW rating (20min)

483.888

AH (c5)

953

AH (c8)

1063.2

AH (c10)

1112

Capacity Bracket (10 Min WPC)

2265 – 2564 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable