12FLB800

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 200 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS / High Rate Multi-Cell VRLA Battery, High Purity Lead Calcium Tin AGM, Thick-Wall ABS case, 12V with (2) M8 threaded insert terminals [792 WPC @15 min to 1.67vpc],[200Ah (c20)], 19.69″L x 8.9″W x 9.25″H (max ht), 140.9 Lbs

Additional information

Weight 140.9 lbs
Dimensions 19.69 × 8.9 × 9.25 in
Product Discontinued?

Yes

Availability

Restricted to European Market Only

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Thick-Wall ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 threaded insert

Terminal Location

Front

Length inches

19.69

Width inches

8.9

Height inches

9.25

Weight in Lbs

140.9

WPC (10min to 1.67vpc @ 25c)

1004

WPC (15min to 1.67vpc @ 25c)

792

WPC (20min to 1.67vpc @ 25c)

639

240-cell kW rating (10min)

240.96

240-cell kW rating (15min)

190.08

240-cell kW rating (20min)

153.36

AH (c20)

200

50% DOD Cycle rating

525

Capacity Bracket (10 Min WPC)

990 – 1064 WPC (10 min)

Capacity Bracket (15 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (20 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems