Description
Switchgear & Control / Telco Battery, High Purity Lead Calcium Tin, Thick Grid Plate AGM, ABS case, 12V with (2) M8 Threaded Insert terminals [390 WPC @15 min to 1.67vpc], [108Ah (c8)], 14.92″L x 6.85″W x 8.54″H (max ht), 81.6 Lbs
Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate
Switchgear & Control / Telco Battery, High Purity Lead Calcium Tin, Thick Grid Plate AGM, ABS case, 12V with (2) M8 Threaded Insert terminals [390 WPC @15 min to 1.67vpc], [108Ah (c8)], 14.92″L x 6.85″W x 8.54″H (max ht), 81.6 Lbs
| Weight | 81.6 lbs |
|---|---|
| Dimensions | 14.92 × 6.85 × 8.54 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M8 threaded insert |
| Terminal Location | Top |
| Length inches | 14.92 |
| Width inches | 6.85 |
| Height inches | 8.54 |
| Weight in Lbs | 81.6 |
| WPC (10min to 1.67vpc @ 25c) | 460 |
| WPC (15min to 1.67vpc @ 25c) | 390 |
| 240-cell kW rating (10min) | 110.4 |
| 240-cell kW rating (15min) | 93.6 |
| AH (c5) | 102 |
| AH (c8) | 108 |
| AH (c10) | 111 |
| Capacity Bracket (10 Min WPC) | 436 – 524 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 376 – 435 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C8 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C10 Ah) | 100 – 199 Ah (C10) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Telecom, Utility Switchgear and Control |