13 GroE 325

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, Pure Lead Flat Plate Plante plate

Description

(Superseded by VX2-325) (13 GroE 325) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (4) Composite Threaded Insert terminals [999.6 WPC @15 min to 1.67vpc],[348Ah (c10), 353.6Ah (c8), 1.22 S.G.], 7.24″L x 13.39″W x 16.14″H (max ht), 115.7 Lbs

Additional information

Weight 115.7 lbs
Dimensions 7.24 × 13.39 × 16.14 in
Product Discontinued?

Yes

Availability

Superseded by VX2-325

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

Pure Lead Flat Plate Plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

7.24

Width inches

13.39

Height inches

16.14

Weight in Lbs

115.7

WPC (10min to 1.67vpc @ 25c)

1170.1

WPC (15min to 1.67vpc @ 25c)

999.6

WPC (20min to 1.67vpc @ 25c)

867.6

240-cell kW rating (10min)

280.824

240-cell kW rating (15min)

239.904

240-cell kW rating (20min)

208.224

AH (c5)

349.5

AH (c8)

353.6

AH (c10)

348

Capacity Bracket (10 Min WPC)

1065 – 1364 WPC (10 min)

Capacity Bracket (15 Min WPC)

990 – 1064 WPC (15 min)

Capacity Bracket (20 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control