14 OPzS1750

Lead Acid Flooded Medium Cycle – Long Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead calcium tubular plate

Description

(Superseded by VL2-1880) Telco/Security/Solar Battery, Flooded Tubular Plate, case, 2V with (6) Composite Threaded Insert terminals [2028Ah (c10)], 8.46″L x 15.75″W x 32.08″H (max ht), 313.7 Lbs

Additional information

Weight 313.7 lbs
Dimensions 8.46 × 15.75 × 32.08 in
Product Discontinued?

Yes

Availability

Superseded by VL2-1880

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium tubular

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

15.75

Height inches

32.08

Weight in Lbs

313.7

WPC (10min to 1.67vpc @ 25c)

2601.2

WPC (15min to 1.67vpc @ 25c)

2505.7

WPC (20min to 1.67vpc @ 25c)

2396.3

240-cell kW rating (10min)

624.288

240-cell kW rating (15min)

601.368

240-cell kW rating (20min)

575.112

AH (c5)

1717

AH (c8)

1939.2

AH (c10)

2028

Capacity Bracket (10 Min WPC)

2565 – 2864 WPC (10 min)

Capacity Bracket (15 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (20 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Long-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control