17 OSP.HC 1445

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-1530) (17 OSP.HC 1445) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (4) Composite Threaded Insert terminals [3082.9 WPC @15 min to 1.67vpc],[1566Ah (c10), 1500Ah (c8), 1.24 S.G.], 8.46″L x 10.91″W x 27.95″H (max ht), 236.8 Lbs

Additional information

Weight 236.8 lbs
Dimensions 8.46 × 10.91 × 27.95 in
Product Discontinued?

Yes

Availability

Superseded by VM2-1530

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

10.91

Height inches

27.95

Weight in Lbs

236.8

WPC (10min to 1.67vpc @ 25c)

3332.9

WPC (15min to 1.67vpc @ 25c)

3082.9

WPC (20min to 1.67vpc @ 25c)

2856

240-cell kW rating (10min)

799.896

240-cell kW rating (15min)

739.896

240-cell kW rating (20min)

685.44

AH (c5)

1349.5

AH (c8)

1500

AH (c10)

1566

Capacity Bracket (10 Min WPC)

3165 – 3464 WPC (10 min)

Capacity Bracket (15 Min WPC)

2865 – 3164 WPC (15 min)

Capacity Bracket (20 Min WPC)

2565 – 2864 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable