18 GroE 1800

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, Pure Lead Flat Plate Plante plate

Description

(Superseded by VX2-1800) (18 GroE 1800) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (6) Composite Threaded Insert terminals [4476.3 WPC @15 min to 1.67vpc],[2091Ah (c10), 2010.4Ah (c8), 1.22 S.G.], 12.99″L x 17.32″W x 23.23″H (max ht), 529.1 Lbs

Additional information

Weight 529.1 lbs
Dimensions 12.99 × 17.32 × 23.23 in
Product Discontinued?

Yes

Availability

Superseded by VX2-1800

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

Pure Lead Flat Plate Plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

12.99

Width inches

17.32

Height inches

23.23

Weight in Lbs

529.1

WPC (10min to 1.67vpc @ 25c)

5007.4

WPC (15min to 1.67vpc @ 25c)

4476.3

WPC (20min to 1.67vpc @ 25c)

4032.8

240-cell kW rating (10min)

1201.776

240-cell kW rating (15min)

1074.312

240-cell kW rating (20min)

967.872

AH (c5)

1854

AH (c8)

2010.4

AH (c10)

2091

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

4365 – 4664 WPC (15 min)

Capacity Bracket (20 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control