240-DDm50-17 (3-Cell Modules)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 480V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS VRLA Modular Battery String, Lead Calcium AGM, configured as 10 stacks of 8 modules, each module w/ (3) VRLA series-connected cells per stackable steel module, Polypropylene case, 480V with (2) Threaded Copper Insert terminals per cell [954 WPC @15 min to 1.67vpc],[420Ah (c10), 400Ah (c8)] 243.7″W x 16.25″D x 78.04″H (max ht), 21120 Lbs

Additional information

Weight 21120 lbs
Dimensions 24.37 × 243.7 × 78.04 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

240

Battery Nominal DC Volts

480

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

24.37

Width inches

243.7

Height inches

78.04

Depth inches

16.25

Weight in Lbs

21120

WPC (10min to 1.67vpc @ 25c)

1078

WPC (15min to 1.67vpc @ 25c)

954

WPC (20min to 1.67vpc @ 25c)

856

240-cell kW rating (10min)

258.72

240-cell kW rating (15min)

228.96

240-cell kW rating (20min)

205.44

AH (c5)

360

AH (c8)

400

AH (c10)

420

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1065 – 1364 WPC (10 min)

Capacity Bracket (15 Min WPC)

915 – 989 WPC (15 min)

Capacity Bracket (20 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems