26 OSP.HC 2730

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-2780) (26 OSP.HC 2730) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (8) Composite Threaded Insert terminals [4797.2 WPC @15 min to 1.67vpc],[2894Ah (c10), 2784.8Ah (c8), 1.24 S.G.], 8.46″L x 19.29″W x 32.09″H (max ht), 481 Lbs

Additional information

Weight 481 lbs
Dimensions 8.46 × 19.29 × 32.09 in
Product Discontinued?

Yes

Availability

Superseded by VM2-2780

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

19.29

Height inches

32.09

Weight in Lbs

481

WPC (10min to 1.67vpc @ 25c)

5150.3

WPC (15min to 1.67vpc @ 25c)

4797.2

WPC (20min to 1.67vpc @ 25c)

4485

240-cell kW rating (10min)

1236.072

240-cell kW rating (15min)

1151.328

240-cell kW rating (20min)

1076.4

AH (c5)

2534

AH (c8)

2784.8

AH (c10)

2894

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

4665 – 4999 WPC (15 min)

Capacity Bracket (20 Min WPC)

4365 – 4664 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable