2AVR45-27 (ILM)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 4V, 696 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 4V module [1521 WPC @15 min to 1.67vpc],[696Ah (c20), 624Ah (c10), 594.4Ah (c8)], 18.25″D x 22.1″W x 9.54″H (max ht), 255 Lbs

Additional information

Weight 255 lbs
Dimensions 22.1 × 22.1 × 9.54 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Location

Front

Length inches

22.1

Width inches

22.1

Height inches

9.54

Depth inches

18.25

Weight in Lbs

255

WPC (10min to 1.67vpc @ 25c)

1762

WPC (15min to 1.67vpc @ 25c)

1521

WPC (20min to 1.67vpc @ 25c)

1365

240-cell kW rating (10min)

422.88

240-cell kW rating (15min)

365.04

240-cell kW rating (20min)

327.6

AH (c5)

535

AH (c8)

594.4

AH (c10)

624

AH (c20)

696

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control