2CX-9M (san)

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 4V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

UPS / Switchgear & Control – High Rate Multi-Cell Flooded Lead-Acid Battery, Lead Calcium Flat Plate, styrene-acrylonitrile case, 4V with (4) Lead Plated Copper Post terminals [401 WPC @15 min to 1.67vpc],[130.4Ah (c8), 1.215 S.G.], 12.2″L x 9″W x 14.8″H (max ht), 72 Lbs

Additional information

Weight 72 lbs
Dimensions 12.2 × 9 × 14.8 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

styrene-acrylonitrile

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

Lead Plated Copper Post

Terminal Location

Top

Length inches

12.2

Width inches

9

Height inches

14.8

Weight in Lbs

72

WPC (10min to 1.67vpc @ 25c)

482

WPC (15min to 1.67vpc @ 25c)

401

WPC (20min to 1.67vpc @ 25c)

361

240-cell kW rating (10min)

115.68

240-cell kW rating (15min)

96.24

240-cell kW rating (20min)

86.64

AH (c5)

125

AH (c8)

130.4

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Utility Switchgear and Control