3 GroE 75

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, Pure Lead Flat Plate Plante plate

Description

(Superseded by VX2-75) (3 GroE 75) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (2) Composite Threaded Insert terminals [230.9 WPC @15 min to 1.67vpc],[80Ah (c10), 81.6Ah (c8), 1.22 S.G.], 7.24″L x 6.1″W x 16.14″H (max ht), 38.6 Lbs

Additional information

Weight 38.6 lbs
Dimensions 7.24 × 6.1 × 16.14 in
Product Discontinued?

Yes

Availability

Superseded by VX2-75

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

Pure Lead Flat Plate Plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

7.24

Width inches

6.1

Height inches

16.14

Weight in Lbs

38.6

WPC (10min to 1.67vpc @ 25c)

270

WPC (15min to 1.67vpc @ 25c)

230.9

WPC (20min to 1.67vpc @ 25c)

200.2

240-cell kW rating (10min)

64.8

240-cell kW rating (15min)

55.416

240-cell kW rating (20min)

48.048

AH (c5)

77.5

AH (c8)

81.6

AH (c10)

80

Capacity Bracket (10 Min WPC)

250 – 324 WPC (10 min)

Capacity Bracket (15 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (20 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control