32 OSP.HC 3360

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium grid low antimony grid plate

Description

(Superseded by VM2-3440) (32 OSP.HC 3360) Premium, Power Plant/UPS/Railway Battery, Flooded Lead Acid, 2V with (8) Composite Threaded Insert terminals [5903.6 WPC @15 min to 1.67vpc],[3554Ah (c10), 3428Ah (c8), 1.24 S.G.], 8.46″L x 22.83″W x 32.09″H (max ht), 572.3 Lbs

Additional information

Weight 572.3 lbs
Dimensions 8.46 × 22.83 × 32.09 in
Product Discontinued?

Yes

Availability

Superseded by VM2-3440

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium grid low antimony grid

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

22.83

Height inches

32.09

Weight in Lbs

572.3

WPC (10min to 1.67vpc @ 25c)

6336.9

WPC (15min to 1.67vpc @ 25c)

5903.6

WPC (20min to 1.67vpc @ 25c)

5520.8

240-cell kW rating (10min)

1520.856

240-cell kW rating (15min)

1416.864

240-cell kW rating (20min)

1324.992

AH (c5)

3121

AH (c8)

3428

AH (c10)

3554

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (20 Min WPC)

5000+ WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable