3AVR45-29 (NIL)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 6V, 750 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [1638 WPC @15 min to 1.67vpc],[750Ah (c20), 672Ah (c10), 640Ah (c8)], 17.5″D x 35.4″W x 9.48″H (max ht), 377 Lbs

Additional information

Weight 377 lbs
Dimensions 35.4 × 35.4 × 9.48 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0030

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

3

Battery Nominal DC Volts

6

Terminal Location

Front

Length inches

35.4

Width inches

35.4

Height inches

9.48

Depth inches

17.5

Weight in Lbs

377

WPC (10min to 1.67vpc @ 25c)

1897

WPC (15min to 1.67vpc @ 25c)

1638

WPC (20min to 1.67vpc @ 25c)

1470

240-cell kW rating (10min)

455.28

240-cell kW rating (15min)

393.12

240-cell kW rating (20min)

352.8

AH (c5)

575

AH (c8)

640

AH (c10)

672

AH (c20)

750

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control