3AVR75-21 (ILM)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 6V, 920 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [1442 WPC @15 min to 1.67vpc],[920Ah (c20), 820Ah (c10), 784Ah (c8)], 25.25″D x 26.4″W x 9.54″H (max ht), 448 Lbs

Additional information

Weight 448 lbs
Dimensions 26.4 × 26.4 × 9.54 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0030

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

3

Battery Nominal DC Volts

6

Terminal Location

Front

Length inches

26.4

Width inches

26.4

Height inches

9.54

Depth inches

25.25

Weight in Lbs

448

WPC (10min to 1.67vpc @ 25c)

1606

WPC (15min to 1.67vpc @ 25c)

1442

WPC (20min to 1.67vpc @ 25c)

1316

240-cell kW rating (10min)

385.44

240-cell kW rating (15min)

346.08

240-cell kW rating (20min)

315.84

AH (c5)

705

AH (c8)

784

AH (c10)

820

AH (c20)

920

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

000 – 1, 1, 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control