Description
Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [1874 WPC @15 min to 1.67vpc],[1200Ah (c20), 1070Ah (c10), 1024Ah (c8)], 24.5″D x 33.15″W x 9.48″H (max ht), 538 Lbs
Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 6V, 1200 Ah (c20), Regulated Valve, lead calcium grid plate
Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [1874 WPC @15 min to 1.67vpc],[1200Ah (c20), 1070Ah (c10), 1024Ah (c8)], 24.5″D x 33.15″W x 9.48″H (max ht), 538 Lbs
| Weight | 538 lbs |
|---|---|
| Dimensions | 33.15 × 33.15 × 9.48 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0030 |
| Battery Chemistry | Lead-Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 3 |
| Battery Nominal DC Volts | 6 |
| Terminal Location | Front |
| Length inches | 33.15 |
| Width inches | 33.15 |
| Height inches | 9.48 |
| Depth inches | 24.5 |
| Weight in Lbs | 538 |
| WPC (10min to 1.67vpc @ 25c) | 2084 |
| WPC (15min to 1.67vpc @ 25c) | 1874 |
| WPC (20min to 1.67vpc @ 25c) | 1710 |
| 240-cell kW rating (10min) | 500.16 |
| 240-cell kW rating (15min) | 449.76 |
| 240-cell kW rating (20min) | 410.4 |
| AH (c5) | 915 |
| AH (c8) | 1024 |
| AH (c10) | 1070 |
| AH (c20) | 1200 |
| 50% DOD Cycle rating | 1800 |
| Capacity Bracket (10 Min WPC) | 1965 – 2264 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 1665 – 1964 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 1665 – 1964 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 500 – 999 Ah (C8) |
| Capacity Bracket (C8 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C10 Ah) | 000 – 1, 1, 999 Ah (C10) |
| Capacity Bracket (C20 Ah) | 000 – 1, 1, 999 Ah (C20) |
| Capacity Bracket (C100 Ah) | 000 – 1, 1, 999 Ah (C100) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium-High |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Data Center UPS Systems, Telecom, Utility Switchgear and Control |