45HR2000S

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 48 Ah (c20), Regulated Valve, lead calcium grid plate

Description

(Discontinued/Superseded) UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, 12V with (2) Tin CU Threaded Insert terminals [168 WPC @15 min to 1.67vpc],[48Ah (c20), 46Ah (c10), 44.8Ah (c8)], 8.89″L x 5.47″W x 8.26″H (max ht), 40 Lbs

Additional information

Weight 40 lbs
Dimensions 8.89 × 5.47 × 8.26 in
Product Discontinued?

Yes

Availability

Superseded by 45HR2000

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Tin CU Threaded Insert

Terminal Location

Top

BCI Reference

22NF

Length inches

8.89

Width inches

5.47

Height inches

8.26

Weight in Lbs

40

WPC (10min to 1.67vpc @ 25c)

216

WPC (15min to 1.67vpc @ 25c)

168

WPC (20min to 1.67vpc @ 25c)

138

240-cell kW rating (10min)

51.84

240-cell kW rating (15min)

40.32

240-cell kW rating (20min)

33.12

AH (c8)

44.8

AH (c10)

46

AH (c20)

48

Capacity Bracket (10 Min WPC)

180 – 249 WPC (10 min)

Capacity Bracket (15 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (20 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (C8 Ah)

20 – 49 Ah (C8)

Capacity Bracket (C10 Ah)

20 – 49 Ah (C10)

Capacity Bracket (C20 Ah)

20 – 49 Ah (C20)

Capacity Bracket (C100 Ah)

50 – 99 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems