4DHR6500S

Lead-Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 198 Ah (c20), Regulated Valve, lead calcium grid plate

Description

(Discontinued/Superseded) UPS High Rate Multi-Cell VRLA Battery, Lead Calcium AGM, 12V with (2) 1/4-20 Brass Insert terminals [624 WPC @15 min to 1.67vpc],[198Ah (c20), 178Ah (c10), 176Ah (c8)], 21.73″L x 8.44″W x 9.34″H (max ht), 129 Lbs

Additional information

Weight 129 lbs
Dimensions 21.73 × 8.44 × 9.34 in
Product Discontinued?

Yes

Availability

Superseded by HR7000ET

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 Brass Insert

Terminal Location

Front

BCI Reference

4D

Length inches

21.73

Width inches

8.44

Height inches

9.34

Weight in Lbs

129

WPC (10min to 1.67vpc @ 25c)

807

WPC (15min to 1.67vpc @ 25c)

624

WPC (20min to 1.67vpc @ 25c)

513

240-cell kW rating (10min)

193.68

240-cell kW rating (15min)

149.76

240-cell kW rating (20min)

123.12

AH (c8)

176

AH (c10)

178

AH (c20)

198

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Capacity Bracket (C100 Ah)

200 – 349 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems