4XTHC-15-P

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 8V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

UPS High Rate Multi-Cell Flooded Lead-Acid Battery, Lead Calcium Plate, Polycarbonate case, 8V with (8) 3/8″ x 1-1/4″ dual bolt hole copper blade posts terminals [2159 WPC @15 min to 1.67vpc, 1.250 S.G.], 16.1″L x 14.32″W x 22.92″H (max ht), 550 Lbs

Additional information

Weight 550 lbs
Dimensions 16.1 × 14.32 × 22.92 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

Polycarbonate

Battery Valve Style

Vented

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

4

Battery Nominal DC Volts

8

Terminal Type

3/8" x 1-1/4" dual bolt hole copper blade posts

Terminal Location

Top

Length inches

16.1

Width inches

14.32

Height inches

22.92

Weight in Lbs

550

WPC (10min to 1.67vpc @ 25c)

2418

WPC (15min to 1.67vpc @ 25c)

2159

WPC (20min to 1.67vpc @ 25c)

1946

240-cell kW rating (10min)

580.32

240-cell kW rating (15min)

518.16

240-cell kW rating (20min)

467.04

Capacity Bracket (10 Min WPC)

2265 – 2564 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1665 – 1964 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems