5 GroE 125

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, Pure Lead Flat Plate Plante plate

Description

(Superseded by VX2-125) (5 GroE 125) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (2) Composite Threaded Insert terminals [384.3 WPC @15 min to 1.67vpc],[134Ah (c10), 136Ah (c8), 1.22 S.G.], 7.24″L x 6.1″W x 16.14″H (max ht), 48.3 Lbs

Additional information

Weight 48.3 lbs
Dimensions 7.24 × 6.1 × 16.14 in
Product Discontinued?

Yes

Availability

Superseded by VX2-125

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

Pure Lead Flat Plate Plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

7.24

Width inches

6.1

Height inches

16.14

Weight in Lbs

48.3

WPC (10min to 1.67vpc @ 25c)

450

WPC (15min to 1.67vpc @ 25c)

384.3

WPC (20min to 1.67vpc @ 25c)

333.7

240-cell kW rating (10min)

108

240-cell kW rating (15min)

92.232

240-cell kW rating (20min)

80.088

AH (c5)

134.5

AH (c8)

136

AH (c10)

134

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control