6-2DDm50-13 (6-Cell Modules)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Control/Solar VRLA Modular Battery String, Lead Calcium AGM, configured as 1 stack of 1 module, each module w/ (6) VRLA series-connected cells per stackable steel module, Polypropylene case, 12V with (2) Threaded Copper Insert terminals per cell [716 WPC @15 min to 1.67vpc],[310Ah (c10), 304Ah (c8)] 34.9″W x 16.25″D x 17.63″H (max ht), 390 Lbs

Additional information

Weight 390 lbs
Dimensions 34.9 × 34.9 × 17.63 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

34.9

Width inches

34.9

Height inches

17.63

Depth inches

16.25

Weight in Lbs

390

WPC (10min to 1.67vpc @ 25c)

809

WPC (15min to 1.67vpc @ 25c)

716

WPC (20min to 1.67vpc @ 25c)

642

240-cell kW rating (10min)

194.16

240-cell kW rating (15min)

171.84

240-cell kW rating (20min)

154.08

AH (c5)

270

AH (c8)

304

AH (c10)

310

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (20 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control