6-2DDm85-15 (2-Cell Modules)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Control/Solar VRLA Modular Battery String, Lead Calcium AGM, configured as 1 stack of 3 modules, each module w/ (2) VRLA series-connected cells per stackable steel module, Polypropylene case, 12V with (2) Threaded Copper Insert terminals per cell [1230 WPC @15 min to 1.67vpc],[610Ah (c10), 600Ah (c8)] 15.43″W x 23.5″D x 34.89″H (max ht), 666 Lbs

Additional information

Weight 666 lbs
Dimensions 15.43 × 15.43 × 34.89 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

15.43

Width inches

15.43

Height inches

34.89

Depth inches

23.5

Weight in Lbs

666

WPC (10min to 1.67vpc @ 25c)

1360

WPC (15min to 1.67vpc @ 25c)

1230

WPC (20min to 1.67vpc @ 25c)

1124

240-cell kW rating (10min)

326.4

240-cell kW rating (15min)

295.2

240-cell kW rating (20min)

269.76

AH (c5)

555

AH (c8)

600

AH (c10)

610

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1065 – 1364 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control