6AVR95-11 (ILM)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 564 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 12V module [923.5 WPC @15 min to 1.67vpc],[564Ah (c20), 497Ah (c10), 475.2Ah (c8)], 27.88″D x 28″W x 9.54″H (max ht), 533 Lbs

Additional information

Weight 533 lbs
Dimensions 28 × 28 × 9.54 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Location

Front

Length inches

28

Width inches

28

Height inches

9.54

Depth inches

27.88

Weight in Lbs

533

WPC (10min to 1.67vpc @ 25c)

1015.2

WPC (15min to 1.67vpc @ 25c)

923.5

WPC (20min to 1.67vpc @ 25c)

848.2

240-cell kW rating (10min)

243.648

240-cell kW rating (15min)

221.64

240-cell kW rating (20min)

203.568

AH (c5)

429

AH (c8)

475.2

AH (c10)

497

AH (c20)

564

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

990 – 1064 WPC (10 min)

Capacity Bracket (15 Min WPC)

915 – 989 WPC (15 min)

Capacity Bracket (20 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control