90G11 (Ultra-High Rate)

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 2V, 500 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte Ultra-High Rate [connectors sized for 670A or less continuous current are NOT INCLUDED] Multi Purpose VRLA single battery cell used with multicell modules, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 2V, [WPC rates to 1.67 VPC: 1119 WPC @5 min, 988 WPC @10 min, 882 WPC @15 min, 796 WPC @20 min, 724 WPC @25 min, 665 WPC @30 min, 536 WPC @45 min, 449 WPC @60 min],[432Ah (c8 / 1.75vpc)], 30.69″W x 8.53″H (max ht) x 23.56″D, 79.5 Lbs

Additional information

Weight 79.5 lbs
Dimensions 30.69 × 8.53 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

30.69

Height inches

8.53

Depth inches

23.56

Weight in Lbs

79.5

WPC (10min to 1.67vpc @ 25c)

988

WPC (15min to 1.67vpc @ 25c)

882

WPC (20min to 1.67vpc @ 25c)

796

240-cell kW rating (10min)

237.12

240-cell kW rating (15min)

211.68

240-cell kW rating (20min)

191.04

AH (c5)

390

AH (c8)

432

AH (c10)

460

AH (c20)

500

50% DOD Cycle rating

2500

Capacity Bracket (10 Min WPC)

915 – 989 WPC (10 min)

Capacity Bracket (15 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (20 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control