E2534024CE02

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 48V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

ms Endur II (AT-25P3x4x2), Multi Purpose Long Life – Multi Rate modular VRLA battery string configured as 2 stacks of 4 modules, ea module w/ (3) VRLA series-connected cells per stackable steel module, Lead Calcium AGM, Polypropylene case, 48V, [2675 wpc @ 15 min to 1.67vpc], [1377.6Ah (c8), 1.300 S.G.], Individual Module dimensions = 30.44″W x 24.75″D x 42.26″H, total system weight = 5320 Lbs

Additional information

Weight 5320 lbs
Dimensions 30.44 × 42.26 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

24

Battery Nominal DC Volts

48

Terminal Location

Front

Width inches

30.44

Height inches

42.26

Depth inches

24.75

Weight in Lbs

5320

WPC (10min to 1.67vpc @ 25c)

2920

WPC (15min to 1.67vpc @ 25c)

2675

WPC (20min to 1.67vpc @ 25c)

2447

240-cell kW rating (10min)

700.8

240-cell kW rating (15min)

642

240-cell kW rating (20min)

587.28

AH (c5)

1260

AH (c8)

1377.6

AH (c10)

1425

Capacity Bracket (10 Min WPC)

2865 – 3164 WPC (10 min)

Capacity Bracket (15 Min WPC)

2565 – 2864 WPC (15 min)

Capacity Bracket (20 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control