LHR12390FT

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 390 watts per cell (15 min), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Battery, Advanced AGM VRLA, ABS case, 12V with (2) T6-A (M8 Top w/M8 front extention) Front terminals [390 WPC @15 min to 1.67vpc], 20″L x 4.33″W x 9.25″H (max ht), 74.96 Lbs

Additional information

Weight 74.96 lbs
Dimensions 20 × 4.33 × 9.25 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T6-A (M8 Top w/M8 front extention)

Terminal Location

Front

Length inches

20

Width inches

4.33

Height inches

9.25

Weight in Lbs

74.96

WPC (10min to 1.67vpc @ 25c)

462

WPC (15min to 1.67vpc @ 25c)

390

WPC (20min to 1.67vpc @ 25c)

316

240-cell kW rating (10min)

110.88

240-cell kW rating (15min)

93.6

240-cell kW rating (20min)

75.84

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems