LHT12-100

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 103.212 Ah (c20), Regulated Valve, high tin lead calcium grid plate

Description

High Temperature Battery, Pure Lead, AGM VRLA, ABS case, 12V with (2) T11 (Female M8) terminals [250.228 WPC @15 min to 1.67vpc],[103.212Ah (c20), 96.82Ah (c10), 92.496Ah (c8)], 12.99″L x 6.81″W x 8.35″H (max ht), 73.85 Lbs

Additional information

Weight 73.85 lbs
Dimensions 12.99 × 6.81 × 8.35 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high tin lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T11 (Female M8)

Terminal Location

Top

BCI Reference

31

Length inches

12.99

Width inches

6.81

Height inches

8.35

Weight in Lbs

73.85

WPC (10min to 1.67vpc @ 25c)

305.03

WPC (15min to 1.67vpc @ 25c)

250.228

WPC (20min to 1.67vpc @ 25c)

215.73

240-cell kW rating (10min)

73.2072

240-cell kW rating (15min)

60.05472

240-cell kW rating (20min)

51.7752

AH (c5)

81.78

AH (c8)

92.496

AH (c10)

96.82

AH (c20)

103.212

Capacity Bracket (10 Min WPC)

250 – 324 WPC (10 min)

Capacity Bracket (15 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (20 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Elevated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Mining, Oil, Utility Switchgear and Control, Water Treatment Plant