LHTF12-150

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 151.34 Ah (c20), Regulated Valve, high tin lead calcium grid plate

Description

High Temperature Battery, Pure Lead, AGM VRLA, ABS case, 12V with (2) T6 (Female M6) terminals [456.37 WPC @15 min to 1.67vpc],[151.34Ah (c20), 142.88Ah (c10), 137.616Ah (c8)], 21.69″L x 4.33″W x 11.34″H (max ht), 102.73 Lbs

Additional information

Weight 102.73 lbs
Dimensions 21.69 × 4.33 × 11.34 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high tin lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T6 (Female M6)

Terminal Location

Front

Length inches

21.69

Width inches

4.33

Height inches

11.34

Weight in Lbs

102.73

WPC (10min to 1.67vpc @ 25c)

560.24

WPC (15min to 1.67vpc @ 25c)

456.37

WPC (20min to 1.67vpc @ 25c)

372.992

240-cell kW rating (10min)

134.4576

240-cell kW rating (15min)

109.5288

240-cell kW rating (20min)

89.51808

AH (c5)

123.61

AH (c8)

137.616

AH (c10)

142.88

AH (c20)

151.34

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Elevated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Mining, Oil, Utility Switchgear and Control, Water Treatment Plant