LP12-250 (Female M8)

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 260 Ah (c20), Regulated Valve, lead calcium grid plate

Description

General Purpose Battery, Lead Calcium AGM, ABS case, 12V with (2) M8 Threaded Insert Top Front terminals [734.5 wpc@15min to 1.67vpc, 260Ah (c20), 250Ah (c10)], 20.6″L x 10.6″W x 8.9″H (max ht), 160.9 Lbs

Additional information

Weight 160.9 lbs
Dimensions 20.6 × 10.6 × 8.9 in
Product Discontinued?

No

Availability

Special Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 threaded insert

Terminal Location

top front

BCI Reference

8D

Length inches

20.6

Width inches

10.6

Height inches

8.9

Weight in Lbs

160.9

WPC (10min to 1.67vpc @ 25c)

918.5

WPC (15min to 1.67vpc @ 25c)

734.5

WPC (20min to 1.67vpc @ 25c)

593.3

240-cell kW rating (10min)

220.44

240-cell kW rating (15min)

176.28

240-cell kW rating (20min)

142.392

AH (c5)

215

AH (c10)

250

AH (c20)

260

Capacity Bracket (10 Min WPC)

915 – 989 WPC (10 min)

Capacity Bracket (15 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (20 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

General Purpose