Description
Telco / Datacenter (UPS) / Utility Switchgear Control Battery, Lead Calcium AGM, ABS case, 12V with (2) M6 Threaded Insert Front terminals [340.8 wpc@15min to 1.67vpc, 100Ah (c8)], 22″L x 4.33″W x 9.17″H (max ht), 78.5 Lbs
Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate
Telco / Datacenter (UPS) / Utility Switchgear Control Battery, Lead Calcium AGM, ABS case, 12V with (2) M6 Threaded Insert Front terminals [340.8 wpc@15min to 1.67vpc, 100Ah (c8)], 22″L x 4.33″W x 9.17″H (max ht), 78.5 Lbs
| Weight | 78.5 lbs |
|---|---|
| Dimensions | 22 × 4.33 × 9.17 in |
| Product Discontinued? | Yes |
| Availability | no longer offered |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94HB-Non-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M6 Threaded Insert |
| Terminal Location | Front |
| BCI Reference | FT-NW-100 |
| Length inches | 22 |
| Width inches | 4.33 |
| Height inches | 9.17 |
| Weight in Lbs | 78.5 |
| WPC (10min to 1.67vpc @ 25c) | 423.6 |
| WPC (15min to 1.67vpc @ 25c) | 340.8 |
| WPC (20min to 1.67vpc @ 25c) | 286.8 |
| 240-cell kW rating (10min) | 101.664 |
| 240-cell kW rating (15min) | 81.792 |
| 240-cell kW rating (20min) | 68.832 |
| AH (c5) | 94.5 |
| AH (c8) | 100 |
| AH (c10) | 103.8 |
| Capacity Bracket (10 Min WPC) | 376 – 435 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 325 – 375 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 250 – 324 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 50 – 99 Ah (C8) |
| Capacity Bracket (C8 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C10 Ah) | 100 – 199 Ah (C10) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Telecom, Utility Switchgear and Control |