LPF12-50 FR

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Telco/Utility/Industrial Standard Battery, AGM VRLA, ABS case, 12V with (2) T6 (M6 top with M6 front extension) Top or Front terminals [172.7 WPC @15 min to 1.67vpc, 50Ah (c10)], 15.35″L x 4.13″W x 7.87″H (max ht), 40.79 Lbs

Additional information

Weight 40.79 lbs
Dimensions 15.35 × 4.13 × 7.87 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T6 (M6 top with M6 front extension)

Terminal Location

Top or Front

Length inches

15.35

Width inches

4.13

Height inches

7.87

Weight in Lbs

40.79

WPC (15min to 1.67vpc @ 25c)

172.7

WPC (20min to 1.67vpc @ 25c)

143.9

240-cell kW rating (15min)

41.448

240-cell kW rating (20min)

34.536

AH (c10)

50

Capacity Bracket (15 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (20 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control