LS12-100

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 108 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Mixed Rate Multi-Cell VRLA Battery, AGM, Thick Lead Calcium Radial Grid Plate, High Impact PVC case, 12V with (2) 1/4-20 Threaded Insert terminals [344 WPC @15 min to 1.67vpc],[108Ah (c20), 103Ah (c10), 100.8Ah (c8), 1.300 S.G.], 16.58″L x 6.84″W x 8.95″H (max ht), 95 Lbs

Additional information

Weight 95 lbs
Dimensions 16.58 × 6.84 × 8.95 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

High Impact PVC

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 Threaded Insert

Terminal Location

Top

Length inches

16.58

Width inches

6.84

Height inches

8.95

Weight in Lbs

95

WPC (10min to 1.67vpc @ 25c)

436

WPC (15min to 1.67vpc @ 25c)

344

240-cell kW rating (10min)

104.64

240-cell kW rating (15min)

82.56

AH (c5)

96

AH (c8)

100.8

AH (c10)

103

AH (c20)

108

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom