LS4-200

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 4V, 214 Ah (c20), Regulated Valve, lead calcium grid plate

Description

(Discontinue) Multi Purpose Long Life – Mixed Rate Multi-Cell VRLA Battery, AGM, Thick Lead Calcium Radial Grid Plate, High Impact PVC case, 4V with (2) 1/4-20 Threaded Insert terminals [688 WPC @15 min to 1.67vpc],[206Ah (c10), 200Ah (c8), 1.300 S.G.], 16.58″L x 6.84″W x 8.95″H (max ht), 95 Lbs

Additional information

Weight 95 lbs
Dimensions 16.58 × 6.84 × 8.95 in
Product Discontinued?

Yes

Availability

Discontinue

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

High Impact PVC

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

1/4-20 Threaded Insert

Terminal Location

Top

Length inches

16.58

Width inches

6.84

Height inches

8.95

Weight in Lbs

95

WPC (10min to 1.67vpc @ 25c)

872

WPC (15min to 1.67vpc @ 25c)

688

240-cell kW rating (10min)

209.28

240-cell kW rating (15min)

165.12

AH (c5)

192

AH (c8)

200

AH (c10)

206

AH (c20)

214

Capacity Bracket (10 Min WPC)

820 – 914 WPC (10 min)

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom