LSe500

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony flat plate

Description

Switchgear / UPS Single-Cell Flooded Lead-Acid Battery, Lead Selenium Plate, 2V with (2) Lead Post with copper insert and 2 holes for dual connector terminals [729.3 WPC @15 min to 1.75vpc, 1 minute discharge current rating to 1.75vpc = 520 amps], [631.2Ah (c24), 530Ah (c10), 503.2Ah (c8)], 5.7″L x 8.1″W x 28.6″H, 100.2 Lbs.

Additional information

Weight 100.2 lbs
Dimensions 5.7 × 8.1 × 28.6 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony flat

Battery Valve Style

Vented

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Lead Post with copper insert and 2 holes for dual connector

Length inches

5.7

Width inches

8.1

Height inches

28.6

Weight in Lbs

100.2

WPC (10min to 1.67vpc @ 25c)

784.5

WPC (15min to 1.67vpc @ 25c)

729.3

WPC (20min to 1.67vpc @ 25c)

683.1

240-cell kW rating (10min)

188.28

240-cell kW rating (15min)

175.032

240-cell kW rating (20min)

163.944

AH (c5)

452

AH (c8)

503.2

AH (c10)

530

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (20 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Utility Switchgear and Control