M87-006-10017-012xxH

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 9.264 kWB (15 min), Regulated Valve, lead calcium grid plate

Description

Absolyte GP Series High Rate [connectors sized for 1044A or less continuous current], (3-100G17 modules), Switchgear & Control Modular Battery String configured as 1 stack of 2 modules, ea module w/ (3) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 12V, [WPC rates to 1.67 VPC: 1743 WPC @10 min, 1544 WPC @15 min, 1392 WPC @20 min, 1268 WPC @25 min, 1173 WPC @30 min, 956 WPC @45 min, 809 WPC @60 min],[800Ah (c8 / 1.75vpc)], 24.5″W x 17.18″H (max ht) x 26.38″D, 847.8 Lbs

Additional information

Weight 847.8 lbs
Dimensions 24.5 × 17.18 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.5

Height inches

17.18

Depth inches

26.38

Weight in Lbs

847.8

WPC (10min to 1.67vpc @ 25c)

1743

WPC (15min to 1.67vpc @ 25c)

1544

WPC (20min to 1.67vpc @ 25c)

1392

240-cell kW rating (10min)

418.32

240-cell kW rating (15min)

370.56

240-cell kW rating (20min)

334.08

AH (c5)

715

AH (c8)

800

AH (c10)

830

AH (c20)

900

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

000 – 1, 1, 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems