M87-012-05005-R19xxMV

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 24V, 120 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 19″ Rack Mount GP Series Medium Rate [connectors sized for 58A or less continuous current] Cellular Station Modular Battery String configured as 1 stack of 2 modules, ea module w/ (6) VRLA series-connected cells per 19″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 24V, [120Ah (c20), 110Ah (c10), 104Ah (c8), 90Ah (c5), 88Ah (c4), 81Ah (c3)], 74Ah (c2)], 58Ah (c1)], 20.31″W x 12.98″H (max ht) x 15.15″D, 264 Lbs

Additional information

Weight 264 lbs
Dimensions 20.31 × 12.98 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

20.31

Height inches

12.98

Depth inches

15.15

Weight in Lbs

264

AH (c5)

90

AH (c8)

104

AH (c10)

110

AH (c20)

120

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Capacity Bracket (C100 Ah)

100 – 199 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control