M87-012-09007-012xxH

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 24V, 300 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte GP Series High Rate [connectors sized for 355A or less continuous current], (6-90G07 modules), Switchgear & Control Modular Battery String configured as 1 stack of 2 modules, ea module w/ (6) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 24V, [WPC rates to 1.67 VPC: 593 WPC @10 min, 529 WPC @15 min, 477 WPC @20 min, 434 WPC @25 min, 399 WPC @30 min, 321 WPC @45 min, 269 WPC @60 min],[256Ah (c8 / 1.75vpc)], 21.69″W x 17.06″H (max ht) x 23.56″D, 632.4 Lbs

Additional information

Weight 632.4 lbs
Dimensions 21.69 × 17.06 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

21.69

Height inches

17.06

Depth inches

23.56

Weight in Lbs

632.4

WPC (10min to 1.67vpc @ 25c)

593

WPC (15min to 1.67vpc @ 25c)

529

WPC (20min to 1.67vpc @ 25c)

477

240-cell kW rating (10min)

142.32

240-cell kW rating (15min)

126.96

240-cell kW rating (20min)

114.48

AH (c5)

235

AH (c8)

256

AH (c10)

270

AH (c20)

300

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control