M87-024-09007-R23xxLV

Lead Acid AGM Float Service Standby – Long Rate limited cycle Stationary Batteries, 48V, 300 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 23″ Rack Mount GP Series Long Rate [connectors sized for 69A or less continuous current] Telco / Cellular Station Modular Battery String configured as 1 stack of 4 modules, ea module w/ (6) VRLA series-connected cells per 23″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 48V, [300Ah (c20), 270Ah (c10), 256Ah (c8), 235Ah (c5), 220Ah (c4), 207Ah (c3)], 24.31″W x 25.96″H (max ht) x 22.48″D, 1128 Lbs

Additional information

Weight 1128 lbs
Dimensions 24.31 × 25.96 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

24

Battery Nominal DC Volts

48

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.31

Height inches

25.96

Depth inches

22.48

Weight in Lbs

1128

AH (c5)

235

AH (c8)

256

AH (c10)

270

AH (c20)

300

50% DOD Cycle rating

2500

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Long-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control