M87-024-09009-R19xxHV

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 48V, 400 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 19″ Rack Mount GP Series High Rate [connectors sized for 423A or less continuous current] Telco / Cellular Station Modular Battery String configured as 1 stack of 6 modules, ea module w/ (4) VRLA series-connected cells per 19″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 48V, [WPC rates to 1.67 VPC: 791 WPC @10 min, 706 WPC @15 min, 636 WPC @20 min, 579 WPC @25 min, 532 WPC @30 min, 429 WPC @45 min, 359 WPC @60 min],[344Ah (c8 / 1.75vpc)], 20.31″W x 38.94″H (max ht) x 22.48″D, 1444.8 Lbs

Additional information

Weight 1444.8 lbs
Dimensions 20.31 × 38.94 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

24

Battery Nominal DC Volts

48

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

20.31

Height inches

38.94

Depth inches

22.48

Weight in Lbs

1444.8

WPC (10min to 1.67vpc @ 25c)

791

WPC (15min to 1.67vpc @ 25c)

706

WPC (20min to 1.67vpc @ 25c)

636

240-cell kW rating (10min)

189.84

240-cell kW rating (15min)

169.44

240-cell kW rating (20min)

152.64

AH (c5)

315

AH (c8)

344

AH (c10)

360

AH (c20)

400

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (20 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

350 – 499 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control