M87-180-GX4000-303xxMV

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 360V, 4000 Ah (c8), Regulated Valve, lead calcium grid plate

Description

Absolyte GX Series Medium Rate [connectors sized for 2616A or less continuous current], (2-GX4000 (FR) modules), UPS Modular Battery String configured as 30 stacks of 3 modules, ea module w/ (2) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 360V, [Ah (c20), 4160Ah (c10), 4000Ah (c8), 3625Ah (c5), 3432Ah (c4), 3174Ah (c3), 2810Ah (c2), 2216Ah (c1)], 1142.7″W x 72.73″H (max ht) x 21.36″D, 125028 Lbs

Additional information

Weight 125028 lbs
Dimensions 1142.7 × 72.73 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

180

Battery Nominal DC Volts

360

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

1142.7

Height inches

72.73

Depth inches

21.36

Weight in Lbs

125028

AH (c5)

3625

AH (c8)

4000

AH (c10)

4160

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems