M87-240-10081-308xxMV

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 480V, 4440 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte GP Series Medium Rate [connectors sized for 2360A or less continuous current], (1-100G81 (FR) modules), UPS Modular Battery String configured as 30 stacks of 8 modules, ea module w/ (3) VRLA parallel-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 480V, [4440Ah (c20), 4050Ah (c10), 3888Ah (c8), 3495Ah (c5), 3324Ah (c4), 3087Ah (c3), 2766Ah (c2), 2028Ah (c1)], 1072.5″W x 68.72″H (max ht) x 26.38″D, 156720 Lbs

Additional information

Weight 156720 lbs
Dimensions 1072.5 × 68.72 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

240

Battery Nominal DC Volts

480

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

1072.5

Height inches

68.72

Depth inches

26.38

Weight in Lbs

156720

AH (c5)

3495

AH (c8)

3888

AH (c10)

4050

AH (c20)

4440

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems