M87-240-GX5000-403xxMV

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 480V, 5000 Ah (c8), Regulated Valve, lead calcium grid plate

Description

Absolyte GX Series Medium Rate [connectors sized for 3270A or less continuous current], (2-GX5000 (FR) modules), UPS Modular Battery String configured as 40 stacks of 3 modules, ea module w/ (2) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 480V, [Ah (c20), 5200Ah (c10), 5000Ah (c8), 4530Ah (c5), 4288Ah (c4), 3966Ah (c3), 3512Ah (c2), 2770Ah (c1)], 1523.6″W x 85.15″H (max ht) x 21.36″D, 201624 Lbs

Additional information

Weight 201624 lbs
Dimensions 1523.6 × 85.15 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

240

Battery Nominal DC Volts

480

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

1523.6

Height inches

85.15

Depth inches

21.36

Weight in Lbs

201624

AH (c5)

4530

AH (c8)

5000

AH (c10)

5200

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C100 Ah)

000+ Ah (C100), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems